962
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-1 Basic Instruction Execution Time
*1. M1536 to M3583, M8256 to M8511, S1024 to S4095
*2. M1536 to M3583, M8000 to M8511
*3. M3584 to M7679
Output instructions
OUT T D 0.71 0.71
T192 to T199, T246 to T511
11.6 µs in execution in ON status
8.2 µs in execution in OFF status
OUT C K 0.71 6.1 0.71 6.1
C235 to C255
9.5 µs in execution in ON status
9.0 µs in execution in OFF status
OUT C D 0.71 6.1 0.71 6.1
C235 to C255
9.5 µs in execution in ON status
9.0 µs in execution in OFF status
SET Y,M 0.065
0.129 µs in 2-step instruction
*2
0.193 µs in 3-step instruction
*3
SET S 4.7 or 6.6 + 0.9n 0.13
n: Number of recombination
4.7 µs when there is no
recombination
RST Y,M 0.065
0.129 µs in 2-step instruction
*2
0.193 µs in 3-step instruction
*3
RST S 4.6 0.13
RST T 0.45 0.45
RST C 0.45 5.8 0.45 4.8
RST D 5.4 0.195
PLS Y,M 0.257 0.321 µs in M3584 to M7679
PLF Y,M 0.257 0.321 µs in M3584 to M7679
Master control instructions
MC 4.3 4.7
MCR 3.9
Other instruction
NOP 0.065
End instruction
END 113.9 + 2.13X + 3.25Y
Even if FEND and END are used
together, execution time of only
END is required.
X: Number of input points
Y: Number of output points
Instruction
Execution time in ON status (µs) Execution time in OFF status (µs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction