EasyManua.ls Logo

Mitsubishi Electric MELSEC FX3U - FNC 66 - ALT; Alternate State

Mitsubishi Electric MELSEC FX3U
1000 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
428
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
14 Handy Instruction – FNC 60 to FNC 69
14.7 FNC 66 – ALT / Alternate State
14.7 FNC 66 – ALT / Alternate State
Outline
This instruction alternates a bit device (from ON to OFF or from OFF to ON) when the input turns ON.
1. Instruction format
2. Set data
3. Applicable devices
S: "D.b" is available only in FX3U and FX3UC PLCs. However, index modifiers (V and Z) are not available.
Explanation of function and operation
1. 16-bit operation (ALT and ALTP)
Alternating output (1-step)
Every time the command input turns ON from OFF, a bit device specified in is alternated (from ON to
OFF or from OFF to ON).
Dividing output (by 2-step alternating output)
Multi-step dividing outputs are achieved by combination of two or more ALTP instructions.
Operand type Description Data type
Bit device number whose output is alternated Bit
Oper-
and
Type
Bit Devices Word Devices Others
System User Digit Specification System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
XYMTCSD
.b KnX KnY KnM KnS T C D R
U\G
VZModifyKH E "
"P
33 3 S 3
P
FNC 66
ALT
Mnemonic Operation Condition
16-bit Instruction
3 steps
ALT
ALTP
Mnemonic Operation Condition
Continuous
Operation
Pulse (Single)
Operation
32-bit Instruction
D
S
2
D
D
1
D
Command
input
FNC 66
ALTP
D
Command input
D
ONON
ON ON ON
1st step
2nd step
Command
input
ON
ONON
ON ON ON
ON
Command
input
FNC 66
ALTP
M0
D
FNC 66
ALTP
M1
D
Specify a same device
M0
D
M0
D
M1