FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
25 Block Data Operation – FNC190 to FNC199
25.3 FNC194~199 – BKCMP=, >, <, < >, <=, >= / Block Data Compare
Caution
When using 32-bit counters (including 32-bit high speed counters)
For comparing 32-bit counters and 32-bit high speed counters (C200 to C255), make sure to use an
instruction for 32-bit operation (DBKCMP=, DBKCMP>, DBKCMP<, DBKCMP<>, DBKCMP<=, or
DBKCMP>=).
If an instruction for 16-bit operation (BKCMP=, BKCMP>, BKCMP<, BKCMP<>, BKCMP<=, or BKCMP>=)
is used, an operation error is caused (error code: K6705).
Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction.
In the case of "DBKCMP = D0 D100 M0 R0", "n" is [R1, R0].
Errors
An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is
stored in D8067.
When the range of "n" ("2n" in 32-bit operation) points starting from and/or exceeds the
corresponding device range (error code: K6706)
When the range of "n" points starting from exceeds the corresponding device range (error code:
K6706)
When data registers starting from specified as "D.b" overlap "n" ("2n" in 32-bit operation) points
starting from (error code: K6706)
When data registers starting from specified as "D.b" overlap "n" ("2n" in 32-bit operation) points
starting from (error code: K6706)
When a 32-bit counter (C200 to C255) is specified in and/or in 16-bit operation (error code:
K6705)
For comparing 32-bit counters, make sure to use an instruction for 32-bit operation (DBKCMP=,
DBKCMP>, DBKCMP<, DBKCMP<>, DBKCMP<=, or DBKCMP>=).