36 Interrupt Function and Pulse Catch Function
36.8 Pulse width/Pulse period measurement function [M8075 to M8079, D8074 to D8097]
*1. The ring counter offers 32-bit data including the most significant bit.
The DSUB (FNC21) instruction does not give a correct value because it handles the most significant
bit as the sign bit. To obtain a correct value, add the processing inside the dotted frame.
2. Cautions on use
The pulse width/pulse period measurement function and input interrupts can be used at the same time in a
same input terminal.
When a same input terminal is used by the pulse width/pulse period measurement function and the SPD
(FNC56), DSZR (FNC150) or ZRN (FNC156) instruction, an operation error occurs when the instruction is
executed.
The input terminal used for the pulse width/pulse period measurement function cannot be used for the
pulse catch function.
When a same input terminal is used by the pulse width/pulse period measurement function and a high
speed counter, a grammatical error occurs.
Make sure that the total frequency of four input channels is 50 kHz or less when using the pulse width/
pulse period measurement function.
When the pulse width/pulse period measurement function and a high speed counter are used together, the
overall frequency of the high speed counter is affected.
For details on high speed counters, refer to Subsection 4.8.7.