26 PARAMETER SETTING
26.2 Module Parameters
Various control specification
Specify the various controls.
Item Description Setting range
Test mode setting
*1
Sets the test mode.
When a problem occurs during data communication with a target device, check
whether or not there is any problem in the operation of the C24.
No specification (other
than test mode)
Hardware test
Self-loopback test
(Default: No specification
(other than test mode))
Communication protocol setting Sets a protocol for communicating with a target device. MELSOFT Connection
MC Protocol (Format 1)
MC Protocol (Format 2)
MC Protocol (Format 3)
MC Protocol (Format 4)
MC Protocol (Format 5)
Nonprocedural protocol
Bidirectional protocol
Predefined protocol
(Default: MELSOFT
Connection)
Communication speed setting Sets a communication rate. Automatically set
*2
1200 bps
2400 bps
4800 bps
9600 bps
14400 bps
19200 bps
28800 bps
38400 bps
57600 bps
115200 bps
230400 bps
(Default: Automatically set)
Transmission
setting
Operation setting
*3
Configures an operation settings of two interfaces. Independent
Interlink
(Default: Independent)
Data bit Sets a bit length for one character in data to be transmitted/received to/from a
target device.
•7
•8
*4
(Default: 7)
Parity bit Set whether or not a parity bit (vertical parity) is added for one character of data
to be transmitted/received.
None
•Yes
(Default: None)
Odd/even parity Sets which parity bit is used, odd parity or even parity, when a parity bit is added.
(This will be enabled only when the parity bit is set to "Yes".)
•Odd
Even
(Default: Odd)
Stop bit Sets a stop bit length for one character in data to be transmitted/received to/from
a target device.
•1
•2
(Default: 1)
Sumcheck code Sets whether or not a sum check code is added to transmission message and
reception message.
None
•Yes
(Default: None)
Online change Sets whether or not data is written to a CPU module during RUN when writing
data from a target device to the CPU module.
Disable
Enable
(Default: Disable)
Setting change Sets whether or not the following processing is allowed after the startup.
Data communication function of each interface, changing of transmission
specification, changing of communication protocol
Writing data to flash ROM
Disable
Enable
(Default: Disable)
Station number setting (CH1, 2 in common:
0 to 31)
Sets the host station number during multidrop communication. 0 to 31
(Default: 0)