26 PARAMETER SETTING
26.2 Module Parameters
431
26
Programmable controller CPU monitoring function setting
Set the system setting value to use the programmable controller CPU monitoring function.
Item Description Setting range
Programmable controller CPU monitoring function designation Sets the timing to transmit the programmable controller
CPU monitoring results to a target device.
• Do not use the function
• Fixed cycle send
• Condition match send
(Default: Do not use the
function)
Cycle time units designation Sets the unit of the cycle time. • 100 ms
• Second
• Minute
(Default: Minute)
Cycle time designation (programmable controller CPU monitoring
interval time)
Set a cycle time.
(The unit depends on the cycle time units designation.)
1 to 65535
(Default: 5)
Send pointer designation Sets the pointer position of the user frame to be
transmitted.
0 to 100
(Default: 0: No designation)
Output quantity designation Sets the number of user frame to be transmitted. 0 to 100
(Default: 0: No designation)
Block monitoring
device
Registered word block quantity designation Sets the number of registered word blocks. 0 to 10
(Default: 0: No designation)
Registered bit block quantity designation Sets the number of registered bit blocks. 0 to 10
(Default: 0: No designation)
CPU error monitoring designation Sets whether or not the monitoring for abnormality on
CPU module is performed.
• Do not monitor
• Monitor
(Default: Do not monitor)
n-th block
monitoring device
*1
Monitoring device
designation
Sets the device code to be monitored. Page 122 List of device
code
(Default: Do not designate)
Start device No.
specification
Sets the start number of device to be monitored. Page 122 List of device
code
(Default: 0)
Number of read
points specification
Sets the read point. 0000H to FFFFH
(Default: 0000H)
Monitoring condition
specification
(judgment condition
specification)
Sets the judgment conditions for the monitoring condition
value.
• Do not designate
• = (Edge)
• <>(Edge)
• <=(Unsigned, Edge)
• <(Unsigned, Edge)
• >=(Unsigned, Edge)
• >(Unsigned, Edge)
• <=(Signed, Edge)
• <(Signed, Edge)
• >=(Signed, Edge)
• >(Signed, Edge)
• =( Level)
• <>( Level)
• <=(Unsigned, Level)
• <(Unsigned, Level)
• >=(Unsigned, Level)
• >(Unsigned, Level)
• <=(Signed, Level)
• <(Signed, Level)
• >=(Signed, Level)
• >(Signed, Level)
(Default: Do not designate)