3 SIGNALS AND WIRING
3.1 Example power circuit connections
33
3
3.1 Example power circuit connections
Precautions
Connect a magnetic contactor between a power supply and the main circuit power supply (L1/L2/L3) of a servo amplifier to
configure a circuit that shuts off the power supply on the servo amplifier side because failure of the servo amplifier may
cause smoke and fire if a magnetic contactor is not connected.
Use a configuration that shuts off the main circuit power supply with ALM (Malfunction).
Check the servo amplifier model and use the correct power supply voltage.
Exogenous noise or lightning surges may degrade the characteristics of the surge absorber (varistor) built into the servo
amplifier and damage it.
Do not shut off the control circuit power supply even if an alarm occurs. If the control circuit power supply is shut off,
network communication will be interrupted.
In the torque mode, EM2 functions the same as EM1.
If using the MR-J5 servo amplifier with the DC power supply input, refer to the following.
Page 38 Using servo amplifier with DC power supply input
To prevent malfunction, avoid bundling the servo amplifier's power lines (input/output) and signal cables together or running
them parallel to each other. Separate the power lines from the signal cables.
Provide adequate protection to prevent an unexpected restart after an instantaneous power failure.
If using a regenerative resistor, configure a circuit that shuts off the main circuit power supply with ALM (Malfunction)
because abnormal overheating of the regenerative resistor may cause smoke and fire.
Configure wiring so that the main circuit power supply is shut off and the servo-on command is turned off after deceleration
to a stop due to an alarm occurrence, an enabled servo forced stop, or a quick stop command from the controller. Use a
molded-case circuit breaker (MCCB) with the input cables of the main circuit power supply.