EasyManua.ls Logo

Mitsubishi Electric NZ2GN2S1-16D - Wiring of Terminal Block for Module Power Supply and FG

Mitsubishi Electric NZ2GN2S1-16D
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 INSTALLATION AND WIRING
6.5 Wiring of Terminal Block for Module Power Supply and FG
127
6
6.5 Wiring of Terminal Block for Module Power Supply
and FG
Tightening torque
Tighten the terminal block mounting screws within the following specified torque range.
Tightening the screws too much may damage the case of I/O module (except for waterproof module).
Wire to be used
The following table describes the wire to be connected to the terminal block for module power supply and FG.
Applicable solderless terminal
The following table lists the applicable solderless terminal.
Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screws with a flathead screwdriver.
To install the terminal block, tighten the terminal block mounting screw with a flathead screwdriver.
Failure to secure the terminal block may cause drop, short circuit, or malfunction.
Screw type Tightening torque range
Terminal block mounting screw (M2.5 screw) 0.2 to 0.3 Nm
Diameter Type Material Temperature rating
22 to 16 AWG Stranded Copper 75 or more
Product
name
Terminal shape Model Applicable wire
size
Bar solderless
terminal tool
Contact
Bar solderless
terminal
Ferrule (with insulation
sleeve)
TE0.5-8, TE0.5-10 0.3 to 0.5 NH-79A NICHIFU Co., Ltd.
TE0.75-8, TE0.75-10 0.75
AI0.34-10TQ 0.34 CRIMPFOX6 PHOENIX CONTACT GmbH &
Co. KG
AI0.5-10WH 0.5
AI0.75-10GY 0.75
Ferrule (without
insulation sleeve)
A0.5-10 0.5
A0.75-10 0.75
A1.0-10 1.0
A1.5-10 1.5

Table of Contents