7 PARAMETER SETTING
7.1 Network Configuration Setting
151
7
7 PARAMETER SETTING
7.1 Network Configuration Setting
Set the parameters of the I/O module with the network parameters written to the CPU module of the master station.
For the setting procedure for the master station, refer to the following.
User's manual for the master station used
Communication cycle interval setting
When using the I/O module in CC-Link IE TSN, set the communication cycle interval setting as follows.
For the I/O module with the firmware version of "03" or later
*1 Set with function setting switch 10. ( Page 120 Function setting switch setting)
*2 To use the I/O module in this combination, set the low speed in the multi-cycle settings of the master station to "x16", and set the
communication cycle setting of the I/O module to "Low-Speed".
*3 To use the I/O module in this combination, do not set the communication cycle setting of the I/O module to "Low-Speed".
For the I/O module with the firmware version of "02"
*1 Set with function setting switch 10. ( Page 120 Function setting switch setting)
*2 To use the I/O module in this combination, set the low speed in the multi-cycle settings of the master station to "x16", and set the
communication cycle setting of the I/O module to "Low-Speed".
*3 To use the I/O module in this combination, do not set the communication cycle setting of the I/O module to "Low-Speed".
For the I/O module with the firmware version of "01"
Communication speed Value that can be set
Master station I/O module
*1
1Gbps 1Gbps When the value is set in increments of 1s: 125.00s or more and 10000.00s or less
When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
100Mbps
*2
When the value is set in increments of 1s: 125.00s or more and 625.00s or less
When the value is not set in increments of 1s: 125.00s, 250.00s, or 500.00s
100Mbps 1Gbps When the value is set in increments of 1s: 125.00s or more and 10000.00s or less
When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
100Mbps
*3
When the value is set in increments of 1s: 500.00s or more, 10000.00s or less, and divisible by 2s
When the value is not set in increments of 1s: 500.00s, 1000.00s, 2000.00s, 4000.00s, or
8000.00s
Communication speed Value that can be set
Master station I/O module
*1
1Gbps 1Gbps When the value is set in increments of 1s: 125.00s or more and 8000.00s or less
When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
100Mbps
*2
When the value is set in increments of 1s: 125.00s or more and 500.00s or less
When the value is not set in increments of 1s: 125.00s, 250.00s, or 500.00s
100Mbps 1Gbps When the value is set in increments of 1s: 125.00s or more and 8000.00s or less
When the value is not set in increments of 1s: 31.25s, 62.50s, 125.00s, 250.00s, 500.00s,
1000.00s, 2000.00s, 4000.00s, or 8000.00s
100Mbps
*3
When the value is set in increments of 1s: 500.00s or more, 8000.00s or less, and divisible by 2s
When the value is not set in increments of 1s: 500.00s, 1000.00s, 2000.00s, 4000.00s, or
8000.00s
Item Value that can be set
Communication cycle interval setting (Not set in units of 1s) 125.00s or more and 8000.00s or less
Communication cycle interval setting (Set in units of 1s)