192
11 TROUBLESHOOTING
11.1 CC-Link IE TSN/CC-Link IE Field Diagnostics
11 TROUBLESHOOTING
This chapter describes error contents that may occur while the I/O module is used and those troubleshooting.
11.1 CC-Link IE TSN/CC-Link IE Field Diagnostics
For CC-Link IE TSN, monitor the status and conduct an operation test.
For details on CC-Link IE TSN/CC-Link IE Field diagnostics, refer to the following.
User's manual for the master station used
Remote reset
Perform the following operation to remotely reset a selected I/O module.
Operating procedure
1. Select a slave station to be reset and click the [Remote Operation] button.
2. Follow the on-screen instructions and click the [Yes] button.
3. Follow the on-screen instructions and click the [OK] button.
Precautions
Remote reset
Remote reset of an I/O module may cause the following because it affects communications on another station.
Another station is disconnected.
A synchronous communication error 1 (error code: 0102H) occurs on another I/O module using the CC-Link IE TSN
Network synchronous communication function.
Setting of function setting switches
When remote reset is performed, if the setting of either of the following function setting switches is different from the setting at
power-on, a Remote reset disable error (error code: 0270H) occurs, and the I/O module is not reset.
Function setting switch 1
Function setting switch 10