6 INSTALLATION AND WIRING
6.8 Wiring of Ethernet Cable
Connecting the Ethernet cable to the I/O module (waterproof module)
Connecting
1. Power off the module power supply of the I/O module (waterproof module) and the power of the external device.
2. Insert the Ethernet cable connector into the I/O module (waterproof module). Pay attention to the connector's orientation.
3. Tighten the Ethernet cable connector.
4. Power on the module power supply of the I/O module (waterproof module).
5. Power on the external device.
6. Check that P1 LINK LED/P2 LINK LED on the port into which the Ethernet cable is connected is on.
*1*2
If P1 LINK LED/P2 LINK LED does not turn on, refer to the following and take a corrective action.
Page 195 When the P1 LINK LED or P2 LINK LED turns off
*1 The time taken for P1 LINK LED/P2 LINK LED to turn on after connection of the Ethernet cable may vary. The LINK LED normally turns
on in a few second. However, if link-up processing is repeated due to a condition of a device on the line, the longer time may be
required.
*2 When connecting a 100Mbps device to P1 and P2 of the I/O module (waterproof module) while the communication speed of the module
is 100Mbps, enable auto-negotiation of the device.
Both P1 and P2 connectors can be used.
To use only one of them for star topology, either P1 or P2 can be connected.
To use both of them for line topology and ring topology, P1-P1, P2-P2, and P1-P2 connections are possible.
Disconnecting
1. Power off the module power supply of the I/O module (waterproof module).
2. Loosen the Ethernet cable connector and remove the cable.