4
[Wiring Precautions]
[Startup and Maintenance Precautions]
[Startup and Maintenance Precautions]
[Disposal Precautions]
CAUTION
Attach waterproof caps to the waterproof/dustproof module to prevent dirt and dust from entering the
module, or prevent the static electricity from causing the module to fail or malfunction.
For waterproof cables used for the waterproof/dustproof module, use UL listed cables in the
categories "CYJV" and "PVVA", with the suitable voltage, current, and temperature rating (the
operating temperature range of the cables: 75 or higher).
Do not replace or wire the waterproof/dustproof module immediately after powering off the system
because the connector parts of the module can get really hot depending on the load conditions.
WARNING
Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction.
Shut off the external power supply (all phases) used in the system before cleaning the module,
retightening the terminal block screws or connector screws, or operating the IP address/station
number setting switches. Failure to do so may cause the module to fail or malfunction.
CAUTION
Do not disassemble or modify the module. Doing so may cause failure, malfunction, injury, or a fire.
Do not drop or apply strong shock to the module. Doing so may damage the module.
Use any radio communication device such as a cellular phone or PHS (Personal Handy-phone
System) more than 25cm away from wiring as well as away in all directions from the programmable
controller. Failure to do so may cause malfunction.
Shut off the external power supply (all phases) used in the system before mounting or removing a
module. Failure to do so may cause the module to fail or malfunction.
After the first use of the product, do not mount/remove the terminal block to/from the module more
than 50 times (IEC 61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
After the first use of the product, do not connect/remove the connector more than 50 times (IEC
61131-2/JIS B 3502 compliant). Exceeding the limit may cause malfunction.
Before handling the module or connection cables, touch a conducting object such as a grounded
metal to discharge the static electricity from the human body. Failure to do so may cause the module
to fail or malfunction.
Startup and maintenance of a control panel must be performed by qualified maintenance personnel
with knowledge of protection against electric shock. Lock the control panel so that only qualified
maintenance personnel can operate it.