7.2.2.2 Controller Settings of Screen Design Software
Item
Set Value
Remarks
GOT NET No.
1
GOT Station No.
18
GOT Communication Port No.
5001
Retry (Times)
3
Startup Time (Sec)
3
Timeout Time (Sec)
3
Delay Time (ms)
0
GOT Ethernet Settings
Item
Set Value
Remarks
Update GOT Ethernet Standard Port
Setting
Checked
GOT IP Address
192.168.3.18
Subnet Mask
255.255.255.0
Default Gateway
0.0.0.0
Peripheral S/W Communication Port No.
5015
Transparent Port No.
5014
7.2.3 Ethernet Controller Settings of Screen Design Software
Host
Net No.
Station
Unit Type
IP Address
Port No.
Communication
1
*
1
1
RCPU *1
192.168.3.39
5006
UDP
*1: Change the models according to the CPU in use.
QCPU: QnUD(P)V/QnUDE(H)
LCPU : LCPU
7.2.4 Routing Information Settings
Routing information settings is required in order to connect to a different network. Set as below.
Transfer Net No.
Relay Net No.
Relay Station No.
CH1
2
1
1
7.2.5 PLC Side Settings (GX Works3)
(1) Go to [Parameter] - [Module Information] and add RJ71GF11-T2.
Set the station type and network number in [RJ71GF11-T2] - [Module Parameter] - [Required Settings]
[Station Type].
Item
Set Value
Remarks
Station Type
Master Station
Network No.
2
(2) Set the network configuration under [Parameter] - [Module Information] - [RJ71GF11-T2]
[Module Parameter] - [Basic Settings] - [Network Configuration Settings]*1.
*1: For QCPU and LCPU, go to [Parameter] - [Network Parameter (Ethernet/CC IE Field)] in GX Works2 and add
CC IE Field (Master Station) to the module 1, and apply the settings above under [CC IE Field Configuration
Setting].
For detail, please refer to the users manual of the devices in use.