EasyManuals Logo

Mitsubishi FX2N User Manual

Mitsubishi FX2N
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
FX2N-32DP-IF Profibus-DP Interface Unit Wiring and Mounting Arrangements 2
2-2
2.2 Wiring
2.2.1 Caution for Wiring
1) Do not lay signal cable near to high voltage power cable or house them in the same trunking
duct. Effects of noise or surge induction may occur. Keep signal cables a safe distance of
more than 100 mm (3.94") from these power cables.
2) Ground the shied wire or the shield of a shielded cable at one point on the programmable
controller. Do not, however, ground at the same point as high voltage lines.
3) The terminal screws of the 32DP-IF are M3.5 (0.14"), therefore the crimp style terminal (see
drawing) suitable for use with these screws should be fitted to the cable for wiring.
Figure 2.3:Crimp Terminals
4) The terminal tightening torque is 0.5 to 0.8 N•m. Tighten securely to avoid malfunction.
5) Cut off all phases of power source before installation or performing wiring work in order to
avoid electric shock or damage of product.
6) Replace the provided terminal cover before supplying power and operating the unit after
installation or wiring work, in order to avoid electric shock.
6.8 mm (0.27" )
or less
For M3.5 (0.14")
6.8 mm (0.27")
or less
For M3.5 (0.14")

Table of Contents

Other manuals for Mitsubishi FX2N

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX2N and is the answer not in the manual?

Mitsubishi FX2N Specifications

General IconGeneral
TypePLC
SeriesFX2N
ManufacturerMitsubishi Electric
Power Supply100-240VAC or 24VDC
Program Capacity8, 000 steps
I/O PointsUp to 256 points
ExpansionYes, via expansion modules
Instruction SetBasic and advanced instructions
Output TypeRelay or Transistor
Humidity5 to 95% RH, non-condensing
CommunicationRS-422, RS-485
Input PointsUp to 128 points
Output PointsUp to 128 points
Execution Speed0.08 µs per instruction
Programming LanguageInstruction List
Data Memory8, 000 words
Operating Temperature0 to 55°C
Storage Temperature-20°C to 70°C