FX2N-32DP-IF Profibus-DP Interface Unit Wiring and Mounting Arrangements 2
2-3
2.2.2 Wiring for 32DP-IF and Profibus-DP Network
To connect the 32DP-IF to a Profibus-DP network use only the Profibus connectors and
shielded twisted-pair cable complying with EN50170.
Please use terminating resistors and Profibus connectors as shown in the DP-master manual
and Profibus connector manual.
The 32DP-IF does not have a terminating resistance built-in.
Figure 2.4:Wiring about 32DP-IF and Profibus-DP Network
Figure 2.5:Wiring for Power Line Circuit
Figure 2.6:Profibus Connector
100 ~ 240 V AC
L COM24+
FX
2N
-32DP-IF
Profibus-DP
Interface Unit
N
Power line
circuit
Service supply
For power circuit,
refer to Figure 2.5.
For Profibus
connector, refer
to Figure 2.6.
Shielded twisted-pair
cable complying with
EN50170 to Profibus-
DP network
Grounding plate
Grounding
resistance of
100
or less
(Class 3)
For noise prevention please attach at least 50 mm
(1.97") of the twisted-pair cable along the grounding
plate to which the ground terminal is connected.
MC
MC
MC
MC
Fuse
Connect to "N" terminals
Power supply
for loads
Power supply
for loads
100 ~ 240 V AC
Emergency stopCircuit protection device
Connect to "L" terminals
Shielded twisted-pair cable to
Profibus-DP network
FX
2N
-32DP-IF Profibus
Interface-DP Unit

Table of Contents

Other manuals for Mitsubishi FX2N

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX2N and is the answer not in the manual?

Mitsubishi FX2N Specifications

General IconGeneral
TypePLC
SeriesFX2N
ManufacturerMitsubishi Electric
Power Supply100-240VAC or 24VDC
Program Capacity8, 000 steps
I/O PointsUp to 256 points
ExpansionYes, via expansion modules
Instruction SetBasic and advanced instructions
Output TypeRelay or Transistor
Humidity5 to 95% RH, non-condensing
CommunicationRS-422, RS-485
Input PointsUp to 128 points
Output PointsUp to 128 points
Execution Speed0.08 µs per instruction
Programming LanguageInstruction List
Data Memory8, 000 words
Operating Temperature0 to 55°C
Storage Temperature-20°C to 70°C

Related product manuals