5.2   Use of stall setting (output when operation is stopped)
Stall output is a constant torque given during the automatic control to the machine while it is stationary.  At 
this stage, the feedback control does not take place.  This torque is the initial torque for the machine to start 
with in the automatic control.
• When Run/stop signal MC1 is turned off to stop the material, the stall memory retains the control output 
values used immediately before the stop.  The system resumes the operation using the memorized 
control output values to stabilize the tension in the material.
The stall memory function is a part of the basic functions, no need to be specially set.
• When changing materials, for example, the stall memory is reset to the output values appropriate to the 
initial material diameter.  These output values are called the stall setting value.
The system uses an EEPROM memory to keep the stall memory values even when the power supply is 
turned off.  No reset operation takes place even when the power supply is turned off or automatic or manual 
modes switching is performed.
• Two methods are available to enter the stall setting value as follow.
• Setting by key input on the operator screen.
• Setting by external analog input.
• To enter the stall setting value by key input on the operator screen, use the “STALL SET” screen.
• To change the stall setting value input by the external analog input setting, refer to page 38.
SA
EAP
P
Internal
stall setting
Selection 
of terminal
MC4
AI3
AI4
-
Large  side:
Preferenced
Tension detection
Target tension
Stall memory
Items in square : Setting on panel surface
Stall memory reset command
Stall setting value
0~100% output against 0~5V 
Memory 
Reading
Torque control output
External 
stall setting
1.  Entering stall setting value
S A L L S E T M E N U #
S E T → # # # % O U T P U T → # # # %
T                
S A L L S E T M E
N
U #
S E T → # # # % T N S N . → # # # # N
T