3. Setup
3 - 84
No. Abbr. Parameter name Details
Setting range
(Unit)
Standard
setting
SP254 DA2NO
D/A output channel 2
data number
Set the output data number for channel 2 of the D/A
output function.
When set to "0", the output is speedometer.
-32768 to
32767
0
SP255
DA1MPY
DA output channel 1
magnification
Set the data magnification for channel 1 of the D/A output
function.
The output magnification is the setting value divided by
256.
When set to "0", the output magnification becomes 1-fold,
in the same manner as when "256" is set.
-32768 to
32767
(1/256-fold)
0
SP256
DA2MPY
DA output channel 2
magnification
Set the data magnification for channel 2 of the D/A output
function.
The output magnification is the setting value divided by
256.
When set to "0", the output magnification becomes 1-fold,
in the same manner as when "256" is set.
-32768 to
32767
(1/256-fold)
0
SP257
to
SP320
RPM*
to
BSD*
Motor constant
(H coil)
This parameter is valid only in the following two
conditional cases:
(a) In case that SP034 (SFNC2) bit0=1
and SP034 (SFNC2) bit2=0
Set the motor constants when using a special motor,
not described in the SP040 (MTYP) explanation and
when not using the coil changeover motor.
(b) In case that SP034 (SFNC2) bit0=1
and SP034 (SFNC2) bit2=1
Set the motor constant of the H coil of the coil
changeover motor.
(Note) It is not allowed for the user to change the setting.
(HEX setting)
0000 to FFFF 0000
SP321
to
SP384
RPML*
to
BSDL*
Motor constant
(L coil)
This parameter is valid only in the following conditional
case:
(a) In case that SP034 (SFNC2) bit0=1
and SP034 (SFNC2) bit2=1
Set the motor constant of the L coil of the coil
changeover motor.
(Note) It is not allowed for the user to change the setting.
(HEX setting)
0000 to FFFF 0000
Parameters with an asterisk * in the abbreviation, such as OSP*, are validated with the NC power turned ON again.