TROUBLESHOOTING
12.3 Error Code List
12.3.3 Error code list (1000 to 1999)
12 - 75
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
1401
There was no response from the
intelligent function module/special
function module in the initial
processing.
The size of the buffer memory of the
intelligent function module/special
function module is invalid.
The unsupported module is mounted.
When the unsupported module is
mounted, remove it.
When the corresponding module is
supported, this suggests the intelligent
function module/special function
module, CPU module and/or base unit
is expecting a hardware fault (Contact
your local Mitsubishi representative.)
QCPU
Rem
When PLC parameter I/O allocation
was being made, there was no return
signal from the special function module
during initial processing stage.(When
error is generated, the head I/O number
of the special function module that
corresponds to the common information
is stored.)
The CPU module, base unit and/or the
special function module that was
accessed is experiencing a hardware
fault. (Contact your local Mitsubishi
representative.)
QnA
1402
The intelligent function module/special
function module was accessed in the
program, but there was no response.
This suggests the intelligient function
module/special function module , CPU
module and/or base unit is expecting a
hardware fault (Contact your local
Mitsubishi representative.)
QCPU
Rem
The special function module was
accessed during the execution of a
FROM/TO instruction set, but there was
no response.
(When an error is generated, the
program error location corresponding to
the individual information is stored.)
The CPU module, base unit and/or the
special function module that was
accessed is experiencing a hardware
fault.(Contact your local Mitsubishi
representative.)
QnA
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 Function version is B or later.
*5 Function version is A.
*6 The module whose first 5 digits of serial No. is 04101 or later.
*7 The module whose first 5 digits of serial No. is 07032 or later.
*8 The module whose first 5 digits of serial No. is 08032 or later.
*9 The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.
*11 The Q13UDHCPU and Q26UDHCPU
*12 This applies to the QnUDE(H)CPU.
*13 The module whose first 5 digits of serial No. is 10042 or later.