2
SYSTEM CONFIGURATION
2.1 System Configuration
2.1.1 System Configuration for Single CPU System
2 - 20
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
GENERAL
SPECIFICATIONS
4
HARDWARE
SPECIFICATIONS OF
THE CPU MODULE
5
POWER SUPPLY
MODULE
6
BASE UNIT AND
EXTENSION CABLE
7
MEMORY CARD AND
BATTERY
8
CPU MODULE START-
UP PROCEDURES
Note1Note2Note3
Table2.2 Restrictions on the system configuration and applicable base units, extension
cables and power supply modules
Maximum number of
extension stages of
extension base units
7 extension stages
Note2.1 Note2.2
Maximum number of
mounted I/O modules
64 modules
Note2.1 Note2.2
Applicable main base
unit model
Q33B, Q35B, Q38B, Q312B
Applicable extension
base unit model
Module types requiring no power supply module
Q52B, Q55B, QA6ADP+A5 B
Note2.3
Module types requiring a Q series power supply module Q63B, Q65B, Q68B, Q612B
Module types requiring an AnS series power supply
module
Note2.3
QA1S65B, QA1S68B
Module types requiring an A series power supply
module
Note2.3
QA65B, QA68B, QA6ADP+A6 B
Extension cable QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q series power supply
module
Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P, Q64PN
AnS series power supply
module
Note2.3
A1S61PN, A1S62PN, A1S63P
A series power supply
module
Note2.3
A61P, A61PN, A62P, A63P, A61PEU, A62PEU
Note1
Note2
Note3
Basic
Note2.1
Universal
UD
Note2.2
High
Performance
Note2.3
When the Q00CPU or Q01CPU is used:
Maximum number of extension stages of the extension base unit : 4 stages
Maximum number of mountable I/O modules : 24 modules
Basic
Note2.1
When the Q02UCPU is used:
Maximum number of extension stages of the extension base unit : 4 stages
Maximum number o Note2.3 f mountable I/O modules : 36 modules
Universal
UD
Note2.2
Usable only when the High Performance model QCPU is used.
Note2.3
High
Performance