MELSEC-Q
4      SETUP AND PROCEDURES BEFORE OPERATION 
 
4.3 Part Identification Nomenclature 
The name of each part of the A/D converter module is listed below. 
 
 
 
Number 
Name and 
appearance 
Description 
1) RUN LED 
Displays the operating status of the A/D converter module. 
On  : Normal operation 
Flickering : During offset/gain setting mode 
Off
  : 5V power supply interrupted, watch dog timer 
error or module exchangeable status during 
online module change bled 
2)  ERR.  LED 
Displays the error status of the A/D converter module. 
On
  : Error
1
 (A/D conversion continues.) 
Flickering : Error
1
 (A/D conversion stops.) 
Off : Normal operation 
3) ALM LED 
Displays the warning status of the A/D converter module. 
On
  : An alarm (process alarm, rate alarm) is being 
generated. 
Flickering : An input signal error is being generated. 
Off : Normal operation 
4) 
Check terminals 
(Q62AD-DGH only) 
Terminal used to check the analog input current value. 
(See Section 4.4.2) 
5) 
External supply 
power terminal 
(Q62AD-DGH only) 
Terminal to connect 24VDC external supply power. 
6)  Serial No. plate  Displays the serial number of the A/D converter module. 
1: Check the error code for details. 
 
POINT 
 
When two or more errors have occurred, the latest error found by the A/D converter 
module is displayed on the LED.