2 - 9                 2 - 9 
MELSEC-Q
2   SYSTEM CONFIGURATION 
 
2.4 Cautions for Power Supply from Q61P-A1/A2 to Q64AD-GH 
When using the Q61P-A1/A2 and Q64AD-GH in combination, it is required to use them 
within the range in Table 2.1. 
This requirement applies to the case where the Q64AD-GH satisfies any of the 
following conditions. 
The first six digits of serial number are "050914" or earlier. 
The first five digits of "Product information" number are "05081" or earlier. 
 
If it satisfies the above conditions but does not meet the ones outlined in Table 2.1, 
carry out the following: 
Replace the power supply module with the Q64P. 
Mount the Q64AD-GH to another base unit. 
 
Table 2.1 Conditions for Use of Q61P-A1/A2 and Q64AD-GH in Combination 
No. of Q64AD-GH 
modules 
Conditions 
Available power supply 
Q61P-A1/A2 Q64P 
3 or less 
Total current consumption of all modules on the same 
base is 5.0A or less. 
   
Total current consumption of all modules on the same 
base exceeds 5.0A. 
   
4 
Module other than the Q64AD-GH is not mounted on 
the same base. 
   
Module other than the Q64AD-GH is mounted on the 
same base. 
   
5 or more 
— 
   
 
1: If the modules are used outside the condition range given in Table 2.1, the "POWER" LED 
of the power supply module may flash*/ and the programmable controller CPU system may 
not start up. 
 
REMARK 
When the Q64AD-GH satisfies any of the following conditions, the above precaution 
does not apply. 
The first six digits of serial number are "051217" or later. 
The first five digits of "Product information" number are "05082" or later.