5.6.5 Pass data (Q62AD-DGH) 
Perform operation in the following sequence to save/restore the user range. 
 
(1)   Switch to the Pass data screen 
Perform the operation in Section 5.6.1 to display the pass data screen. 
 
 
 
(2)   User range saving 
(a)   Change the Setting value field of pass data read request to "Request", and 
click the   Execute test 
 button. 
When read is completed, the values are displayed in the Current value fields 
of CH
 industrial shipment settings offset/gain values/CH  user range 
settings offset/gain values. 
 
(b)   Compare the values with those in the range reference table, and record 
them if they are correct. 
Refer to Section 7.4 for the range reference table. 
 
(3)   User range restoration 
(a)   Set the recorded values in the Setting value fields of CH  industrial 
shipment settings offset/gain values/user range settings offset/gain values. 
 
(b)   Select all the Setting value fields of CH
 industrial shipment settings 
offset/gain values/user range settings offset/gain values, and click the 
 Execute test 
 button. 
When write is completed, the set values are displayed in the Current value 
fields of CH
 industrial shipment settings offset/gain values/ CH  user 
range settings offset/gain values. 
 
(c)   Change the Setting value field of pass data write request to "Request", and 
click the   Execute test 
 button. 
Make sure that the indication in the Current value field of pass data write 
request changes from "Request" to "OFF" on completion of write.