5 - 26                   5 - 26 
MELSEC-Q
5   UTILITY PACKAGE (GX Configurator-AD) 
 
(3)   User range restoration 
(a)   Set "Voltage specified" or "Current specified" in the Setting value field of 
Pass data classification setting, and click the   Execute test 
 button. 
When the setting is completed, the set data is displayed in the Current value 
field of CH
 Pass data classification setting. 
 
(b)   Set the recorded values in the Setting value fields of CH
 Industrial 
shipment settings offset/gain values/user range settings offset/gain values. 
 
(c)   Select all the Setting value fields of CH
 Industrial shipment settings 
offset/gain values/user range settings offset/gain values, and click the 
 Execute test 
 button. 
When write is completed, the set values are displayed in the Current value 
fields of CH
 Industrial shipment settings offset/gain values/CH  User 
range settings offset/gain values. 
 
(d)   Change the Setting value field of Pass data write request to "Request", and 
click the   Execute test 
 button. 
Make sure that the indication in the Current value field of Pass data write 
request changes from "Request" to "OFF" on completion of write.