3 - 23                                                                                    3 - 23 
MELSEC-Q
3   SPECIFICATIONS 
 
3.2.4 Warning output function 
(1)   Process alarm 
(a)      If the detected digital output value rose to or above the process alarm 
upper upper limit value or fell to or below the process alarm lower lower limit 
value and entered the warning output range, the warning output flag (buffer 
memory address 48: Un\G48) and warning output signal (X8) turn ON and 
the ALM LED is lit to indicate the warning. 
 
(b)      If, after the output of the warning, the detected digital output value fell 
below the process alarm upper lower limit value or rose above the process 
alarm lower upper limit value and returned to within the setting range, "0" is 
stored into the bit position corresponding to the channel number of the 
warning output flag (buffer memory address 48: Un\G48). 
The warning output signal (X8) turns OFF only when all channels return to 
within the setting range. 
 
(c)      When time or count averaging is specified, this function is executed at 
intervals of the preset averaging time or averaging count. 
When any other A/D conversion system (sampling processing, move 
averaging, primary delay filter) is specified, this function is executed at 
intervals of the sampling time.