EasyManua.ls Logo

Mitsubishi Q62AD-DGH - 7.3.3 When user range setting is used and initial setting was made with GX Configurator-AD (other system is available)

Mitsubishi Q62AD-DGH
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 - 14 7 - 14
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.3 When user range setting is used and initial setting was made with GX Configurator-AD
(other system is available)
(1) Conversion disable
(a) Disable the conversion by the following procedures.
1) Set the A/D conversion enable/disable setting (buffer memory address
0: Un\G0) for all channel conversion disable (F
H
).
2) Turn on Operating condition setting request (Y9) to stop the
conversion.
3) Operating condition setting completed flag (X9) is turned off.
4) Check that the conversion stops with the actual analog output value.
5) Turn off Operating condition setting request (Y9).