3 - 64                                                                                    3 - 64 
MELSEC-Q
3   SPECIFICATIONS 
 
3.4.19 CH   rate alarm upper/lower limit value (buffer memory addresses 122 to 137: 
Un\G122 to Un\G137) 
(1)      Set the varying rate range of the digital output value for each channel. 
 
(2)      To make the setting valid, the operating condition setting request (Y9) must be 
turned ON/OFF. (Refer to Section 3.3.2.)
 
 
(3)      The setting range is -65536 to 65535 (-6553.6 to 6553.5%). Set the value in 
0.1%/s increments.
 
Example)    When setting the rate alarm upper limit value to 30%/s, store 300 into 
the buffer memory. 
 
(4)      Refer to Section 3.2.4 for details of the rate alarm. 
 
POINT 
 
The channel where the value outside the above setting range has been written 
results in an error, the error code is stored into the Error code (buffer memory 
address 19: Un\G19), the error flag (XF) turns ON, and the rate alarm is executed 
at the pre-error setting.