4 - 7                                                                                    4 - 7 
MELSEC-Q
4      SETUP AND PROCEDURES BEFORE OPERATION 
 
(2)   Q62AD-DGH 
 
(a) For 2-wire transmitter input 
 
 
 
(b) For current input 
 
*1:  Use a 2-core twisted shielded wire for the power wire. 
*2: Shows input resistance. 
*3:  To connect with the 2-wire transmitter, be sure to connect to P and I/CHK+. 
*4:  Always use a ground. In addition, ground the FG of the power supply module. 
*5:  The check terminals (I/CHK+, CHK-) are used to check the amount of input in 
mA in relation to the 2-wire transmitter output. This can be checked since 
analog inputs of 4 to 20mA are converted to analog outputs of 1 to 5V. The 
relationship of this conversion can be expressed by the following formula: 
 
*6:  Open the relay terminal surely because, the power supply for 2-wire 
transmitter is always on.