EasyManua.ls Logo

Mitsubishi Q62AD-DGH - Page 61

Mitsubishi Q62AD-DGH
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 - 32 3 - 32
MELSEC-Q
3 SPECIFICATIONS
Device No. Signal Name Description
XA
Offset/gain
setting mode flag
[In offset/gain setting mode]
(1) This signal is used as an interlock condition to turn ON/OFF the User range writing
request (YA) when the value at completion of offset/gain setting adjustment is
registered.
(2) See Section 4.6 regarding the offset/gain settings.
OFF
Module ready (X0)
Offset/gain setting mode flag (XA)
User range writing request (YA)
Performed by the A/D converter module
Performed by the sequence program
[In normal mode]
(1) This signal is used as an interlock condition to turn ON/OFF the User range writing
request (YA) when the user range is restored.
(2) Refer to Chapter 7 for the user range restoration.
ON
Performed by the A/D converter module
Performed by the sequence program
Module ready (X0)
Offset/gain setting mode flag (XA)
User range writing request (YA)

Table of Contents