3 - 41 3 - 41
MELSEC-Q
3 SPECIFICATIONS
Table 3.8 Buffer memory assignment of Q64AD-GH (3/5)
Address
Description
Default
value
Read/Write
1
Reference
Hexadecimal Decimal
4EH 78
System area
to to
55H 85
56H 86
CH1 Process alarm lower lower limit value (L)
(H)
0 R/W
2
Section
3.4.17
57H 87
58H 88
CH1 Process alarm lower upper limit value (L)
(H)
0 R/W
2
59H 89
5AH 90
CH1 Process alarm upper lower limit value (L)
(H)
0 R/W
2
5BH 91
5CH 92
CH1 Process alarm upper upper limit value (L)
(H)
0 R/W
2
5DH 93
5EH 94
CH2 Process alarm lower lower limit value (L)
(H)
0 R/W
2
5FH 95
60H 96
CH2 Process alarm lower upper limit value (L)
(H)
0 R/W
2
61H 97
62H 98
CH2 Process alarm upper lower limit value (L)
(H)
0 R/W
2
63H 99
64H 100
CH2 Process alarm upper upper limit value (L)
(H)
0 R/W
2
65H 101
66H 102
CH3 Process alarm lower lower limit value (L)
(H)
0 R/W
2
67H 103
68H 104
CH3 Process alarm lower upper limit value (L)
(H)
0 R/W
2
69H 105
6AH 106
CH3 Process alarm upper lower limit value (L)
(H)
0 R/W
2
6BH 107
6CH 108
CH3 Process alarm upper upper limit value (L)
(H)
0 R/W
2
6DH 109
6EH 110
CH4 Process alarm lower lower limit value (L)
(H)
0 R/W
2
6FH 111
70H 112
CH4 Process alarm lower upper limit value (L)
(H)
0 R/W
2
71H 113
72H 114
CH4 Process alarm upper lower limit value (L)
(H)
0 R/W
2
73H 115
74H 116
CH4 Process alarm upper upper limit value (L)
(H)
0 R/W
2
75H 117
76H 118 CH1 Rate alarm warning detection period 0 R/W
2
Section
3.4.18
77H 119 CH2 Rate alarm warning detection period 0 R/W
2
78H 120 CH3 Rate alarm warning detection period 0 R/W
2
79H 121 CH4 Rate alarm warning detection period 0 R/W
2
7AH 122
CH1 Rate alarm upper limit value (L)
(H)
0 R/W
2
Section
3.4.19
7BH 123
7CH 124
CH1 Rate alarm lower limit value (L)
(H)
0 R/W
2
7DH 125

Table of Contents