3 - 45 3 - 45
MELSEC-Q
3 SPECIFICATIONS
(2) Buffer memory assignment of Q62AD-DGH
POINT
Do not write data from system area or sequence program to the buffer memory
area where writing is disabled. Doing so may cause malfunction.
Table 3.9 Buffer memory assignment of Q62AD-DGH (1/4)
Address
Description
Default
value
Read/Write
1
Reference
Hexadecimal Decimal
0H 0 A/D conversion enable/disable setting 0003H R/W
2
Section
3.4.2
1H 1
CH1 Average time/Average number of times/Move average/
Time constant settings
0 R/W
2
Section
3.4.3
2H 2
CH2 Average time/Average number of times/Move average/
Time constant settings
0 R/W
2
3H 3
System area
4H 4
5H 5 CH1 A/D conversion starting time setting 30 R/W
2
Section
3.4.4
6H 6 CH2 A/D conversion starting time setting 30 R/W
2
7H 7
System area
8H 8
9H 9 Averaging process specification 0 R/W
2
Section
3.4.5
AH 10 A/D conversion completed flag 0 R
Section
3.4.6
BH 11 CH1 Digital output value(16Bit) 0 R Section
3.4.7
CH 12 CH2 Digital output value(16Bit) 0 R
DH 13
System area
to to
12H 18
13H 19 Error code 0 R
Section
3.4.8
14H 20 Setting range 0 R
Section
3.4.9
15H 21 System area
16H 22
Offset/gain setting mode
offset specification
0 R/W
Section
3.4.10
17H 23
Offset/gain setting mode
gain specification
0 R/W
18H 24
System area
to to
1DH 29
1EH 30 CH1 Maximum value(16Bit) 0 R/W
2
Section
3.4.11
1FH 31 CH1 Minimum value(16Bit) 0 R/W
2
20H 32 CH2 Maximum value(16Bit) 0 R/W
2
21H 33 CH2 Minimum value(16Bit) 0 R/W
2
22H 34
System area
to to
2EH 46
2FH 47
Input signal error detection extended/input signal error
detection/warning output settings
0333
H R/W
2
Section
3.4.12
30H 48 Warning output flag 0 R
Section
3.4.13
31H 49 Input signal error detection flag 0 R
Section
3.4.14