3 - 40 3 - 40
MELSEC-Q
3 SPECIFICATIONS
Address Decimal
(Hex)
Protocol
CH1 CH2
Application Name
Initial
value
MC Non Bi Pd
Registration
Reference
section
16688
(4130H)
18480
(4830H)
0: No log
Upper 8 bits: Second
Lower 8 bits: Minute
Second (00
H
to 59
H
) Minute (00
H
to 59
H
)
b15 b8 b7 b0to to
0 — R
16689
(4131H)
18481
(4831H)
Execution
log 1
End
time
and
date
0: No log
Lower 8 bits: First 2 digits of year
Lower 8 bits: Day of week
Day of week (00H to 06H)Year (00H to 99H), first 2 digits
00
H (Sunday) to 06H (Saturday)
b15 b8 b7 b0to to
0 — R
16690 to
18177
(4132H to
4701H)
18482 to
19969
(4832H to
4E01H)
Checking
protocol
execution logs
Execution
log 2 to 32
Same as Execution log 1 0 R
Not allowed
Section 8.1.4,
Operating
Manual
(Pre-defined
protocol
support
function)
18178 to
18429
(4702H to
47FDH)
19970 to
20223
(4E02H to
4EFFH)
20224 to 20479
(4F00H to 4FFFH)
Use prohibited System area
20480 to 24575
(5000H to 5FFFH)
Send/receive
area for pre-
defined protocol
function
Pre-defined protocol function buffer 0 RW Not allowed
Operating
Manual
(Pre-defined
protocol
support
function)
24576 to 32767
(6000H to 7FFFH)
Use prohibited System area
1 The following (a) and (b) show assignments of block monitoring device areas No.
1 to No.10 for the programmable controller CPU monitoring function (CH1 side:
8272 to 8361 (2050
H to 20A9H), CH2 side: 8528 to 8617 (2150H to 21A9H)).
2 In the pre-defined protocol mode, the area can be used as a user setting area (the
send and receive data storage areas).
3 For the QJ71C24(-R2), the initial value of 0H is set for both CH1 and CH2.