EasyManua.ls Logo

Mitsubishi QJ71C24N - Reading the RS-232 Control Signal Status

Mitsubishi QJ71C24N
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 - 10 11 - 10
MELSEC-Q
11 TROUBLESHOOTING
11.1.3 Reading the RS-232 control signal status
This section explains how to read the control signal status stored in the buffer memory
during communication using RS-232 interface.
When GX Configurator-SC is used, check the status using the "Transmission control
and others monitor/test" screen (see Section 9.6.3).
When a transmission problem occurs, read operation is executed to check the signal
on/off status of the RS-232 interface.
(1) RS-232 control signal status (address: 254H/264H)
The status of the RS-232 signals is stored as follows:
REMARKS
(1) For more details on signals for RS-232, see Section 3.2.1.
(2) Signals output from the Q series C24 side (RS(RTS) and ER(DTR)) are
controlled by the operating system (OS) of the Q series C24.
They cannot be directly controlled by the sequence program.
(3) There is a maximum delay of 100 ms in signal status stored in the buffer
memory above.
(2) Example of a program that reads from RS-232 control signal status
(address: 254
H/264H)
The following shows an example of a program that reads the RS-232 control
signal status.
(input/output signals X/Y00 to X/Y1F of the Q series C24)
Example of FROM instruction

Table of Contents

Related product manuals