The following shows the RS-422/485 cable specification.
(1) Use a 1200 m (3937 ft.), or shorter, cable that satisfies the following specification
for the RS-422/485 cable (cable to connect the Q series C24 terminal block).
Item Description
Cable type Shielded cable
Number of pairs 3P
Conductor resistance (20 °C)
88.0
/km or less
Insulation resistance
10000 M
- km or more
Dielectric strength 500 V DC, 1 minute
Electrostatic capacitance (1 kHz) 60nF/km or less on average
Characteristic impedance (100 kHz)
110 ± 10
Recommended conductor size 0.2 mm
2
to 0.75 mm
2
Diameter AWG22 to AWG16
Type Stranded wire
Material Copper wire
Temperature rating 60°C or more
(Recommended cable)
SPEV (SB)-MPC-0.2
3P ..... (MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-0.2
3P .............. (MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-MPC-0.2 3P and SPEV (SB)-0.2 3P have the same electrical
characteristics, but different external diameter and internal wire colors.
(2) Make the total distance within 1200 m (3937 ft.) when two or more device are