EasyManua.ls Logo

Mitsubishi QJ71C24N - Page 111

Mitsubishi QJ71C24N
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 - 8 4 - 8
MELSEC-Q
4 SETTINGS AND PROCEDURES PRIOR TO OPERATION
(c) When connecting the terminal resistor of the QJ71C24N-R4 to the plug-in
terminal block of the RS-422/485, insert the terminal resistor as shown below.
Correct insertion
Inserted vertically.
Incorrect insertion
Inserted horizontally.
POINT
1) When an RS-232 to RS-422 converter is used at a terminal station on the line, a
terminal resistor must be connected and set at the converter.
2) When connecting the external device(s) and serial communication module(s)
with RS-232 to RS-422 converter(s), the converters must support the system
configurations (1:1, 1:n, and m:n).
3) To the RS-422/485 interface of the serial communication module, an RS-422 or
RS-485 device must be connected, including the cases of 1:n, n:1 and m:n
connections.