Loading...
9 - 20 9 - 20
MELSEC-Q
9 UTILITY PACKAGE (GX Configurator-SC)
[Setting Items]
The following table shows the selection menus for system setting/registration to
be displayed:
Function Section Remarks
User frame registration Section 9.4.1
Data for modem initialization registration Section 9.4.2
Data for modem connection registration Section 9.4.3
Modem function system setting Section 9.4.4
Transmission control and others system setting Section 9.4.5
MC protocol system setting Section 9.4.6
Non procedure system setting Section 9.4.7
Bidirectional system setting Section 9.4.8
Pre-defined protocol system setting Section 9.4.9
PLC CPU monitoring system setting Section 9.4.10
Transmission user frame No. designation system setting Section 9.4.11
Can be used via online
operation.
Can be used via offline
operation.
Resetting buffer memory/flash ROM setting values to default values Section 9.4.12
Flash ROM write allow/prohibit setting Section 9.4.13
Can be used only via online
operation.
POINT
(1) The ASCII codes are listed in Appendix 4 and GX Configurator-SC's Help
function. Use the list as a reference.
(2) The values set in the respective setting screens explained in Section 9.4 can
be written to the Q series C24 module (via online operation only) or saved to a
file.
(3) Perform the following operations in advance to enable the registration of
setting values in the flash ROM:
(a) Switch setting using the GX Developer (see Section 4.5.2)
Set "Setting change" under [Transmission settings] to "Enable" for both
the CH1 and CH2 sides.
(b) Setting using GX Configurator-SC (see Section 9.4.13)
Set the flash ROM write allow/prohibit setting to "Allowed".
(4) When a multiple CPU system is employed, GX Configurator-SC should be
connected to the control CPU of the Q series C24, and the system setting data
register in the flash ROM.
It is not possible to set target PLC to multiple CPU setting of "Transfer setup"
of GX Developer and register the system setting data in the flash ROM.

Table of Contents