MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7164H Request error
Either the request or the device
designation method is wrong.
Check the transmission
message/request from the external
device, make the necessary
corrections, and send again.
7166H System error
The OS of the Q series C24 detected
some error.
(1)
7167H
A write command was designated when
"Disable write during RUN" was set.
C/N
Change the setting to "Enable write
during RUN" and restart data
communications.
7168H
Cannot execute a
command during
RUN
A command that cannot be executed
during RUN was designated.
C/N
Stop the CPU and restart data
communications.
7169H CPU error
Cannot communicate normally with the
CPU.
C/N
If there is an error in the CPU, remove
the CPU error and restart data
communications.
716AH
to
716B
H
System error
The OS of the Q series C24 detected
some error.
(
1)
The Q series C24 used is not
compatible with the Built-in Ethernet
port QCPU.
To use a Built-in Ethernet port QCPU,
use a Q series C24 of function version
B or later, and the first 5 digits of its
serial No. must be 10042 or greater.
716CH System error
The OS of the Q series C24 detected
some error.
( 1)
716DH
Monitor data was not written using QnA
compatible 2C/3C/4C frame.
PRO
716EH
Monitor data write
error
Monitor data was not written using A
compatible 1C frame.
PRO
Rewrite monitor data.
716FH Device error
A nonexistent device was designated.
Device that cannot be specified by the
corresponding command was
designated.
PRO
Check and correct the external device
transmit message and restart data
communications.
7170H
Number of access points exceeded the
range.
PRO
7171H
A device that cannot be designated was
designated.
PRO
7172H
A compatible 1C
frame error
Written number of monitoring points is
incorrect. For example, [0] was
designated.
PRO
Check and correct the external device
transmit message and restart data
communications.
7173H
Monitor data write
error
Monitor data was written for a CPU
other than a Q/QnACPU using QnA
compatible 2C/3C/4C frame.
PRO
Write the monitor data and use the A
compatible 1C frame to a CPU other
than a Q/QnACPU.
7D00H
Protocol No. setting
error
In control data of the CPRTCL
instruction, the specified protocol No. is
out of range.
CHn
ERR.
Correct the protocol No. setting.
7D01H
Continuous protocol
execution count
setting error
The number of protocols to be executed
continuously, which is specified with an
argument in the CPRTCL instruction, is
out of range.
CHn
ERR.
Correct the value set for the number of
protocols to be executed continuously.
7D02H
Protocol not-ready
error
The protocol was executed while Pre-
defined protocol ready (X1D) is OFF.
The CPRTCL instruction was executed
during protocol setting data writing.
The CPRTCL instruction was executed
with abnormal protocol setting data.
CHn
ERR.
Confirm Pre-defined protocol ready
(X1D) turned ON before executing the
CPRTCL instruction.
To prevent concurrent execution of the
CPRTCL instruction, set the CPU to
STOP before writing the protocol setting
data.
Write the protocol setting data again to
the Q series C24N, and then execute
the CPRTCL instruction.
If this error persists even after rewriting,
replace the module.