EasyManua.ls Logo

Mitsubishi QJ71C24N - Page 340

Mitsubishi QJ71C24N
442 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 - 24 11 - 24
MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
Cannot write to Flash ROM normally.
7E57H
Flash ROM write
error
Power is turned off during writing to
Flash ROM.
CHn
ERR.
Re-execute the write operation.
If the error is generated again, replace
the module.
7E58H
Mode modification
error
There was an error in the mode No. or
transmission specification designated
contents when changing the mode.
PRO
Check and correct the contents of the
external device transmit message and
restart data communications.
Recheck the switch setting on the Q
series C24.
Writing to flash ROM was performed
1000 times after power-on.
Review the program.
Reset the Flash ROM write count
(address: 2401
H) to 0 and restart data
communications.
7E59H
Flash ROM write
count over limit error
Writing to flash ROM was performed
100,000 times.
CHn
ERR.
When the number of writes reached
100,000, replace the module.
7E5EH
Programmable
controller CPU
monitoring function
registration error
The programmable controller CPU
monitoring function is registered for the
communication protocol that does not
support the function.
CHn
ERR.
Correct the communication protocol
setting value.
7E5FH
I/O number error on
requested module
I/O number of requested module is
incorrect.
Correct the I/O number of the module to
which data is sent.
7E60H
Device monitoring
duplicate registration
error
Programmable controller CPU
monitoring registration was performed
twice.
Cancel the programmable controller
CPU monitoring and perform the
programmable controller CPU
monitoring registration again.
7E61 H
Cycle time units
range error
Setting value of cycle time units is out of
range.
Correct the setting value of the cycle
time units.
7E62 H
Programmable
controller CPU
monitoring function
error
Setting value of programmable
controller CPU monitoring function is
out of range.
Correct the setting value of the
programmable controller CPU
monitoring function.
7E63 H
Transmission
measure setting
error
Setting of transmission measure of the
programmable controller CPU
monitoring is incorrect.
Correct the setting value of the
transmission measure.
7E64 H
Registration point
range error
Registration point (word/bit) is out of
range.
Correct the setting value of the
registration point (word/byte)
7E65 H
Programmable
controller CPU
abnormal monitoring
number error
Setting value of the programmable
controller CPU abnormal monitoring is
out of range.
Correct the setting value of the
programmable controller CPU abnormal
monitoring.
7E66 H
Monitoring condition
error of monitoring
device
Setting value of transmission condition
is out of range.
Correct the setting value of the
transmission condition.
7E67 H
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU
abnormal monitoring is out of range.
Correct the setting value (fixed value) of
the CPU abnormal monitoring.
7E68H
Transmission
condition range error
of monitoring device
Setting value of transmission condition
(condition agreement transmission) is
out of range.
Correct the setting value of the
transmission condition (condition
agreement transmission).
7E69H
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU
abnormal monitoring is out of range.
Correct the setting value (fixed value) of
the CPU abnormal monitoring.
7E6AH
Monitoring device
read point range
error
Read point of monitoring device is out
of range.
Correct the setting value of the read
point of the monitoring device.
7E6BH
7E6CH
7E6DH
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU
abnormal monitoring is out of range.
Correct the setting value (fixed value) of
the CPU abnormal monitoring.
7E6EH System error
The OS of the Q series C24 detected
some error.
(1)
7E6FH
Modem connection
error
Modem is connected to an incorrect
channel.
Correct the C
H to which notification is
sent.

Table of Contents