Loading...
11 - 28 11 - 28
MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7F91H
to
7F96
H
7F98H
to
7F9A
H
7F9DH
7F9EH
7FA0H
to
7FA3
H
7FA8H
7FAAH
to
7FAD
H
7FAFH
to
7FB2
H
7FB5H
7FB6H
7FB8H
to
7FBC
H
7FC0H
to
7FC4
H
System error
The OS of the Q series C24 detected
some error.
(
1)
7FC8H
Protocol setting data
error
There is an error in the protocol setting
that was edited in GX Configurator-SC
(Pre-defined protocol support function).
The protocol setting data written to the
Q series C24N includes unsupported
function data.
The protocol setting data written to the
Q series C24N is corrupted.
CHn
ERR.
Identify the incorrectly edited protocol in
Protocol setting data error information
(buffer memory: 4086
H to 4089H),
correct the setting data, and write them
again to the Q series C24N.
Check the version of the Q series C24N
to confirm the supported functions. Use
the pre-defined protocol function within
the range of supported functions.
Write the protocol setting data again to
the Q series C24N, and execute the
CPRTCL instruction.
If this error persists even after rewriting,
replace the module.
7FC9H
to
7FCF
H
System error
The OS of the Q series C24 detected
some error.
(
1)
7FD0H
to
7FE5
H
Refer to the error code list for use of the modem function, and take corrective action. (Refer to Section 11.2.3.)
7FE6H Remote passwords do not match.
Check the remote password and
communicate again.
7FE7H
The remote password is not registered.
The remote password processing
command was received on the interface
side where the modem function is not
used.
The GX Developer connection is
selected in the communication protocol
setting on the corresponding CH.
CHn
ERR.
A remote password processing
command is not necessary when a
remote password is not registered.
Perform a remote password unlock
processing through GX Developer.
Alternatively, change the
communication protocol setting of the
corresponding CH to the MC protocol.
7FE8H
Processing disabled
The number of remote password
disagreements exceeded the value
designated at the address 200D
H.
CHn
ERR.
Clear the storage area of the
accumulated cout of unlock process
abnormal completion processing
(address: 22FC
H) to 0.
7FE9H
Refer to the error code list for use of the modem function, and take corrective action. (Refer to Section 11.2.3.)
7FEFH Switch setting error
There is an error in the switch setting by
the GX Developer
CHn
ERR.
Write CPU to the parameter and reboot
after correcting the setting value for the
switch.

Table of Contents