3 - 13 3 - 13
MELSEC-Q
3 SPECIFICATIONS
[Example of setting in sequence program]
MOV K1 D0
H1C2 D0 K1T0 H0
Send command
Set echo back to "Disable".
Set the value in the echo back
enable/disable setting area
(address: 450 (1C2H)).
Data transmission program
POINT
The echo back enable/disable setting must be done before sending data.
Any setting changed during transmission does not take effect.