EasyManua.ls Logo

montwill M2 - Page 29

montwill M2
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. Setting up the device
26
Menu level Parameterisation level
Alerting relay 2,
Default:
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either
be inserted at activated alarms or deactivated alarms . If is
selected, logical links are available in the menu level and . Access to
these two menu levels is via , at all other selected functions, these two
parameters are overleaped. Via the setpoints can be activated/deactivated,
in this case the output and the setpoint display are set/not set on the front of the
device. The parameters , and can only be used in accordance with
the semi-automatic calibration (Chapter 8. Sensor alignment). At the relay
switches during sensor calibration, at during offset calibration and at
during the calibration of the final value. With [P] the selection is confirmed and the
device changes into menu level.
Logic relay 2,
Default:
Here, the switching behavior of the relay is defined via a logic link, the following
schema describes these functions with inclusion of and : This parameter
can only be selected if was selected under .
A1 v A2 As soon as a selected alarm is activated, the
relay operates. Equates to operating current
principle.
A1 v A2 = A1 Λ A2 The relay operates only, if no selected alarm
is active. Equates to quiescent current
principle.
A1 Λ a2 The relay operates only, if all selected alarms
are active.
A1 Λ A2 = A1 v A2 As soon as a selected alarm is not activated,
the relay operates.
With [P] the selection is confirmed and the device changes into menu level.
____ _ _
____ _ _
….
….

Related product manuals