User’s Manual
225-748-00P
August 2024
Default/Factory Configuration
The following are the default factory settings for your unit.
Input: 4-wire RTD, Pt3850, 100 ohm, 0-100° C
*Lower Out of Range Value: -1.00 Deg C (1% of Span)
*Upper Out of Range Value: 101 Deg C (1% of Span)
*Startup Delay: 0 Seconds
Scale Mode: Off
Trim Mode: Factory Trim
Trip Alarms: Trip Point 50° C, Deadband 0, High Alarm, Non-Latching, 0 Delay
*Input Fault Alarm: Latching (On)
*Manual Reset: Trip Alarms 1 & 2 Only
Optional Analog Output (AO): Current, No Damping, Fail Low, Scaled to 4-20mA
Display: Process Variable (PV), Auto Decimal Point, 60Hz Filter
Broken Wire Detection: Level Set to 0 (disabled)
Password: 1
Note: *For STA units with rmware versions 1.5 and earlier, these defaults are not
congurable.
Programmable RTD, T/C, Ohms, mV and Potentiometer Safety Trip Alarm
STA
TPRG
SECTION 1