Programmable RTD, T/C, Ohms, mV and Potentiometer Safety Trip Alarm
STA
TPRG
SECTION 4
Reset Fault
Figure 4.13 gives an overview of the Reset Fault menu.
1. At “RESET FAULT”, press SELECT.
2. Use the UP or DOWN buttons to alternate between “RESET NO?” and “RESET YES?”.
Press SELECT.
3. The “CONFG EXIT” option appears. Press SELECT , to exit Main Configuration Menu or
use the UP and DOWN buttons cycle through Main Configuration Menu.
RESET FAULT will clear all input related faults. All unit faults must be cleared by power cycling
the unit. If a fault is still present after these steps, please contact Customer Service for further
assistance. Refer to Table 6.1 for a full list of STA diagnostic messages and corrective actions.
RESET
FAULT
CONFG EXIT
Selection:
RESET YES?
RESET NO?
SEL
SEL
Figure 4.13. RESET FAULT