www.miinet.comMoore Industries-International, Inc.
- 73 -
User’s Manual
225-748-00P
August 2024
www.miinet.com
Section 9 - Specications
Performance
Adjustments
Weight
Indicators
Ambient
Conditions
Performance
of Analog
Output
(-AO option)
Performance
of Analog
Output
(-AO option)
(contnued)
0-20mA 0, 23.6mA
4-20mA 3.6, 23.6mA
X-20mA
(0<X<4)
Output
Failure Limits
(90% of X), 23.6mA
* Power Supply options no longer available for purchase
9.4
9.1
9.3
9.2
Input Accuracy and Alarm Trip Repeatability:
Refer to Table
Overall Accuracy: The overall accuracy
of the unit is the combined input and output
accuracies. It includes the combined eects of
linearity, hysteresis, repeatability and adjustment
resolution. It does not include ambient
temperature eect. For T/C input, add the RJC
error.
Reference Junction Compensation Accuracy
(T/C inputs only): ±0.45°C
Stability: Refer to Table
Dead Band: User-set within selected input
range; fully scalable and set in user-selected
engineering units
Input to Output Trip Response Time: 256msec
maximum from step change on input to alarm
state change when alarm is set to trip at mid-point
of step
Alarm Trip Delay: Programmable from 0-120
seconds (0-60 seconds for rmware versions
1.1.2 and earlier)*
Isolation: 500Vrms between case, input, output,
and power
Dielectric Strength: 1966Vdc for 2 seconds,
between case, input, output, and power
Power Supply: Universal 21.6-375Vdc or
90-260Vac; *24DC range, 18-30Vdc;
*UAC range, 90-260Vac
Power Consumption:
5W Maximum for Universal; 3.5W maximum for
DC supply; 4W maximum for UAC supply
Power Supply Eect: ±0.002% of span per 1%
line voltage change
Input Over-Range Protection: ±5Vdc, maximum
Input Resistance: T/C and mV inputs, 40Mohms,
nominal
Excitation Current: RTD and Ohms, 250
microamps, ±10%
Output Relays
Dual Process Relays and One Fault Relay
(Relays are single-pole/double-throw SPDT,
1 form C, rated 3A@250Vac or 3A@30Vdc,
50/60Hz, non-inductive)
Analog Output Option
Output Accuracy: Current, ±0.01% of maximum
span (±2 microamps); Voltage, ±0.01% of
maximum span (±1mV)
Input to Output Response Time: 256msec for
the output to change 10% to 90% of its scale for
an input step change of 0 to 100%
Output Step Response Time: 100msec
maximum
Output Ripple (up to 120Hz): 50mV peak-to-
peak maximum on voltage output; 10mV peak-to-
peak measured across a 250 ohm load resistor
for current output (frequencies up to 120Hz)
Analog Output Range: Current Output 0-21.6mA,
Minimum Span 4mA; Voltage
Output -0.2-10.5V; Minimum Span 1V
Output Current Limiting:
Current outputs:
Voltage output:
Failure Limit: -0.50 -11.0V
Load Capability: Source mode (internal power
supply), 0-1 kohms for current output; 2 kohms
for voltage output; Sink Mode (External power
Supply), 42Vdc Max
Load Eect (current outputs): ±0.01% of span
from 0 to maximum load resistance on current
output
Operating Range:
-40°C to +85°C
(-40°F to +185°F)
Relay Range:
-40°C to +85°C
(-40°F to +185°F)
Storage Range:
-40°C to +85°C
(-40°F to +185°F)
Ambient Temperature Eect: Refer to Table
Eect of Ambient Temperature on Reference
Junction Compensation (T/C inputs
only): ±0.005°C per °C change of ambient
temperature;
With Analog Output: ±0.009% of
maximum span/°C
Relative Humidity: 5-95%, non-condensing
RFI/EMI Protection:
20V/m@80-1000MHz, 1kHz AM, when tested to
IEC61326
Noise Rejection: Common Mode,
100dB@50/60Hz
Normal Mode,
refer to Table
Front panel push-buttons for parameter
congurations; Internal jumper and menu
password protect parameter settings
LCD: 2x5 14-segment characters, backlit,
alphanumeric readout accurate to the nearest
digit.
Range: -99999 to 99999; Decimal point can be
user-set
LED Type:
INPUT LED:
Dual color LED indicates input
failure
READY LED: Green LED indicates unit is
operating properly
ALARM 1 and 2 LED: Dual color LED per relay
indicates alarm status
FAULT LED: Green LED indicates unit is
operating properly; Red LED indicates unit has
fault or is latched.
Display Accuracy:
±1 digit; when scaling the display (or in custom
mode), high input-to-display span ratios
decrease display accuracy
527 g to 581 g
(18.6 oz to 20.5 oz)
Programmable RTD, T/C, Ohms, mV and Potentiometer Safety Trip Alarm
STA
TPRG
SECTION 9