14
3.7.2. Alarms
All alarms are activated by default.
Any alarm that is activated immediately appears on the screen.
To dismiss an alarm : press the OK or button (short or long press, depending on the alarm).
MESSAGE
DISPLAYED
/ FAULT
DETECTED
IMMEDIATE
AUTOMATIC
ACTION
CAUSE
CHECKS AND REMEDIES
OPTION TO
DEACTIVATE
VIA THE
MENU
« Parameters -
Alarms »
Stopping
production
Alarm
Cell Current
Yes
Cell problem.
Check that the cell is not scaled.
Inspect and adjust if necessary the
inversion frequency of the current
supplying the cell Electrolysis -
Inversion » menu).
Check that the electrical connections to
the terminals of the cell are sufficiently
tight and not oxidised.
Check that the cell's power cable is in
good condition.
Check that the cell's power cable
connector is correctly connected to the
electronics unit.
As a last resort, replace the cell.
No
MESSAGE
DISPLAYED /
FAULT
DETECTED
IMMEDIATE
AUTOMATIC
ACTION
CAUSE
CHECKS AND REMEDIES
OPTION TO
DEACTIVATE
VIA THE
MENU
« Parameters -
Alarms »
Stopping
production
Alarm
Flow
Yes
Insufficient water
flow through the
filtration circuit.
Check that :
the flow sensor is connected to the
electronics unit.
the flow sensor is activated Parameters -
Sensors » menu).
the valves on the filtration circuit are open.
the filtration pump is working correctly.
the filtration circuit is not blocked.
there is enough water in the pool.
No
Alarm
Com. Failure
Yes
Loss of
communication
between the
control board
and the power
board of the
electronics unit.
Contact a professional.
No
Alarm
No water
Yes
Insufficient
amount of water
in the filtration
circuit.
Check that the filtration pump is running
correctly.
Yes