Repair Section
80
8.2 Removal of Refrigeration System Components
WARNING
Before replacing any refrigeration cycle component, recover the refrigerant using
standard recovery procedures and equipment.
When recovering the refrigerant, use the pinch-off tubes at the low pressure side (tube 1)
and high pressure side (tube 2) as shown in the figure below.
CAUTION
To prevent oxidation, dry nitrogen should be conducted {flow rate 0.27 gal/min (1 L/min)} through
the pinch-off tube during any brazing operation.
During any component replacement involving brazing, shield nearby parts with a steel plate, etc.,
to protect them from the flame.
< NOTE >
When replacing the compressor, attach the pipe 1 and the pipe 2 packaged in the compressor
assembly.
ILL00668-00
F
E
G
J
Pipe 2
Pipe 1
Tube 1
Tube 2
H
D
C
B
Part to Replace
• Compressor
• Condenser
Electronic Expansion Valve
• Evaporator
Disconnect at
E, F, G, H
B, C
• High Pressure Switch J
C, D
A, I
I
A