ioLogik E1200 Series RESTful API Default Address Mappings
C-2
RESTful API Name Description Access
/api/slot/0/io/di/0/diCounterValue diCounterValue DI - Counter mode - value read-only
/api/slot/0/io/di/0/diCounterReset DI - Counter mode - reset
to initial value (1: RESET)
read-write
/api/slot/0/io/di/0/diCounterStatus DI - Counter mode - status
(0: STOP, 1: START)
read-write
/api/slot/0/io/do
/api/slot/0/io/do doIndex DO - index read-only
/api/slot/0/io/do doMode DO - mode (0: DO, 1:
Pulse)
read-only
/api/slot/0/io/do doStatus DO - DO mode - status (0:
OFF, 1: ON)
read-write
/api/slot/0/io/do doPulseCount DO - Pulse mode - count read-write
/api/slot/0/io/do doPulseOnWidth DO - Pulse mode -
ON width
(unit: 1 ms)
read-write
/api/slot/0/io/do doPulseOffWidth DO - Pulse mode - OFF
width (unit: 1 ms)
read-write
/api/slot/0/io/do doPulseStatus DO - Pulse mode - status
(0: STOP, 1: START)
read-write
/api/slot/0/io/do/0/doStatus doStatus DO - DO mode - status (0:
OFF, 1: ON)
read-write
/api/slot/0/io/do/0/doPulseCount doPulseCount DO - Pulse mode - count read-write
/api/slot/0/io/do/0/doPulseStatus doPulseStatus DO - Pulse mode - status
(0: STOP, 1: START)
read-write
/api/slot/0/io/relay
/api/slot/0/io/relay relayIndex Relay - index read-only
/api/slot/0/io/relay relayMode Relay - mode (0: Relay, 1:
Pulse)
read-only
/api/slot/0/io/relay relayStatus Relay - Relay mode -
status
(0: OFF, 1: ON)
read-write
/api/slot/0/io/relay relayTotalCount Relay - Relay mode - total
count
read-only
/api/slot/0/io/relay relayCurrentCount Relay - Relay mode -
current count
read-only
/api/slot/0/io/relay relayCurrentCountReset Relay - Relay mode - reset
current count (1: RESET)
read-write
/api/slot/0/io/relay relayPulseStatus Relay - Pulse mode -
status
(0: STOP, 1: START)
read-write
/api/slot/0/io/relay relayPulseCount Relay - Pulse mode - count read-write
/api/slot/0/io/relay relayPulseOnWidth Relay - Pulse mode - ON
width (unit: 1.5 s)
read-write
/api/slot/0/io/relay relayPulseOffWidth Relay - Pulse mode - OFF
width (unit: 1.5 s)
read-write
/api/slot/0/io/relay/0/relayStatus relayStatus Relay - Relay mode -
status
(0: OFF, 1: ON)
read-write
/api/slot/0/io/relay/0/relayPulseStatus relayPulseStatus Relay - Pulse mode -
status
(0: STOP, 1: START)
read-write
/api/slot/0/io/relay/0/relayPulseCount relayPulseCount Relay - Pulse mode - count read-write
/api/slot/0/io/ai
/api/slot/0/io/ai aiIndex AI - index read-only
/api/slot/0/io/ai aiMode AI - mode (0: 0-10 V, 1:
4-20mA, 2: 0-20mA, 4:
4-20mA burnout)
read-only

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1214-T and is the answer not in the manual?

Moxa Technologies ioLogik E1214-T Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E1214-T
CategoryI/O Systems
LanguageEnglish

Related product manuals