6 Mounting
Maschinenfabrik Reinhausen GmbH 2023 394001150/12 EN MSENSE
®
DGA 2/3
6.3.1 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan-
dards. The following points must be observed in order to maintain the EMC
standards.
▪ The system's overvoltage protection must be effective.
▪ The system's ground connection must comply with all technical regula-
tions.
▪ For signal transmission, use shielded leads with individual conductors
(outgoing conductor / return conductor) twisted in pairs.
▪ Connect full surface of shielding to device or to a nearby grounding bar.
6.3.2 Cable recommendation
Please note the following Maschinenfabrik Reinhausen GmbH recommenda-
tion when wiring the device.
Excessive line capacitance can prevent the relay contacts from interrupting
the contact current. In control circuits operated with alternating current, take
into account the effect of the line capacitance of long control cables on the
function of the relay contacts.
The connection cables used must comply with a temperature resistance
within the permissible ambient temperature range of -40...+60°C.
Cable Terminal** Cable type Max. length
Power supply 1, 2, 3 Unshielded
Analog outputs 4…12 Shielded 400m (<25Ω/km)
Relay* 13…27 Unshielded
Table6: Recommendation for connection cables
*) Observe line capacitance.
**) Also refer to Terminal technical data [►Section 13, Page 90].
6.3.3 Routing and preparing the cables
Consider the position of the connections when preparing the cables (see
chapter Electrical connection [►Section 14.4, Page 97]).
Ensure that the length of the PE conductor (terminal3) is at least 50mm
longer than the supply voltage conductors (terminals1 and 2).