13 Technical data
Maschinenfabrik Reinhausen GmbH 202390 4001150/12 ENMSENSE
®
DGA 2/3
13 Technical data
Measurement
Application Determination of the gas concentration of fault gases as well as
moisture in oil and oil temperature of mineral-based transformer
insulating oil in accordance with IEC60296:2012 /
ASTMD3487-09
Measured vari-
ables
H
2
CO
(only for
MSENSE
DGA 3)
Humidity Oil temper-
ature
Relative
display can
be
switched
Absolute
display can
be
switched
Lower detection
limit
15ppm 25ppm 3% RH 5ppm -20°C
Upper detection
limit
2,000ppm 2,000ppm 90% RH 2,000ppm +115°C
Measuring accu-
racy
±10%
1, 2
or
3
±20ppm
±15%
1, 2
or
3
±20ppm
±1.8% RH
5
±2%
4
±1°C
Repetition accu-
racy
±5%
2
or
3
±10ppm
±5%
2
or
3
±10ppm
±1%RH ±1%
4
±1°C
Sensor resolution 1ppm 1ppm 1% RH n.a. 1°C
1
Determination based on IEC60567, AppendixE
2
Of the measured value
3
Depending on which value is larger
4
Of the saturation curve; IEC60422
5
At +23°C
Conditions of use
Locations of use Indoors and outdoors, all climate zones
Installation altitude Up to 4,000m above sea level
Offshore Optional
Mounting location Directly on the transformer tank or in the
oil closed circuit cooling pipe; installation
horizontal
Operating temperature
6
-40...+60°C
Insulating fluid temperature
6, 7
-20...+115°C
DGA measuring range with respect to
the operating temperature
6
-20...+60°C
DGA measuring range with respect to
the temperature of the insulating fluid
6, 7
+10...+90°C
Ambient humidity 0...100%RH
Storage temperature -40...+80°C