7 Commissioning
Maschinenfabrik Reinhausen GmbH 202354 4001150/12 ENMSENSE
®
DGA 2/3
Limit value Default*) Minimum Maximum
Gas formation rate too high alarm 50ppm/d 0ppm/d 80ppm/d
4mA signal setting 15ppm 15ppm 1,999ppm
20mA signal setting 1,000ppm 16ppm 2,000ppm
Table8: Hydrogen (H2) limit values
*) Recommended values based on IEEEC57.104, Condition1
Moisture (H2O) limit values
Limit value Default Minimum Maximum
Concentration too high warning 30% RH 0% RH 100% RH
Concentration too high alarm 45% RH 0% RH 100% RH
Gas formation rate too high warning 10% RH/d 0% RH/d 100% RH/d
Gas formation rate too high alarm 15% RH/d 0% RH/d 100% RH/d
4mA signal setting 3% RH 3% RH 99% RH
20mA signal setting 100% RH 1% RH 100% RH
Table9: Moisture (H2O) limit values
7.4.2 General settings
Proceed in accordance with the description in the MESSKO®MSET param-
eterization software operating instructions in order to adjust the following
listed settings where necessary.
Measurement interval setting
The measurement interval is the time between 2 measurements (in hours).
The shortest measurement interval is 3hours.
Measurement interval
Standard value 6hours
Maximum value 24hours
Minimum value 3hours
H2O reference setting
The analysis results of the MESSKO® oil laboratory or an equivalent labora-
tory can be entered here in order to make a comparison between the water
content (H2O in ppm) of the MSENSE® DGA 2/3 analysis and that of the
laboratory. A field comparison for the gases H2 and CO is performed in the
service area of the MSET software (see chapter Maintenance [►Section 10,
Page 67]).