14 Appendix
Maschinenfabrik Reinhausen GmbH 202398 4001150/12 ENMSENSE
®
DGA 2/3
14.5 Data point table for Modbus RTU
Separate input register
No. Address Size Description Designation
1 0 1byte On / Off CO limit 1
2 1 1byte On / Off CO limit 2
3 2 1byte On / Off H
2
limit 1
4 3 1byte On / Off H
2
limit 2
5 4 1byte On / Off H
2
O limit 1
6 5 1byte On / Off H
2
O limit 2
7 6 1byte On / Off CO rate limit 1
8 7 1byte On / Off CO rate limit 2
9 8 1byte On / Off H
2
rate limit 1
10 9 1byte On / Off H
2
rate limit 2
11 10 1byte On / Off H
2
O rate limit 1
12 11 1byte On / Off H
2
O rate limit 2
13 12 1byte On / Off Maintenance in 6months
14 13 1byte On / Off Maintenance required
15 14 1byte On / Off CO Value Valid
1)
16 15 1byte On / Off H
2
Value Valid
1)
17 16 1byte On / Off H
2
O Value Valid
1)
18 17 1byte On / Off H
2
O Mode %RH
1)
If the "Value Valid = Off" status is present, it means the same as an aster-
isk (*) in the display or in the MSET status display, and the system is outside
the specified measuring range in accordance with the "Technical
data" [Section 13, Page 90] chapter. The following applies to the transmit-
ted measured value:
During the first measurement after the running-in phase, the value of the
lower detection limit is transmitted.
If measured values within the specified measuring range have already
been recorded, then the last valid measured value is transmitted.
If the status changes to "Value Valid = On", then the system is back in the
valid measuring range.